Guidelines for Extension Cord Use
Extension cords are only to be used for temporary
purposes. They do not replace the need for installation
of outlets and proper wiring where necessary
Many questions have arisen regarding the restrictions on extension
cords on campus. The following guidelines should be used by students
and staff to assure that the extension cords in use do not violate
good safety practices or fire codes. The National Electric Code
(NEC) is the primary document that provides guidance in the use
of extension cords. These guidelines are based on the NEC.
In dormitories and office settings:
- Extension cords which have the UL label are approved, so
long as the size and use is appropriate.
- Two and three conductor extension cords must have a minimum
conductor size of 16 AWG copper.
- Extension cords are normally rated in amps, and must be used
within the ampere rating. (Compare the ampere rating of the
appliance with the rating of the chord.)
- Three pronged (three conductor) extension cords must be used
when connecting electrical items that have three pronged
plugins.
- Extension cords must not be run under rugs, mattresses, through
doorways or windows, and must be protected from damage at
all times.
- Three prong adapters are not to be used with two conductor
extension cords on the female end of the cord. Adapters used
on the wall outlet must be installed with a metal screw installed
in the outlet. (Contact Facilities Management for these installations.
x6.7570)
- Splicing and "home repairs" of extensions cords
are not permitted unless performed by Facilities Management.
Insulation, strength and conductor size must not be compromised.
- Cords used in wet and/or outdoor locations should be protected
by ground fault circuit interrupters.
On maintenance and construction sites:
- Extension cords with an equipment grounding conductor must
be used at all times.
- Extension cords must be protected from damage, and not run
through doorways or windows where the doors or windows may
close, causing damage to the cord.
- Extension cords must be plugged into a circuit protected
by a ground fault circuit interrupter on wet or outdoor construction
and maintenance sites, or have the ground circuit checked
for continuity in an assured grounding and conductor program.
- Extension cords should be a minimum of 16 AWG and be rated
for the equipment in use. The following is a guide that might
be helpful in selecting the cord:
| Extension
Cord Ampere Rating |
Wire Size
(Copper) |
Single
Phase Two and Three Conductor Cords |
Three
Phase Cords |
| 16 AWG |
13 amps |
10 amps |
| 14 AWG |
18 amps |
15 amps |
| 12 AWG |
25 amps |
20 amps |
| 10 AWG |
30 amps |
25 amps |
| 8 AWG |
40 amps |
35 amps |
| 6 AWG |
55 amps |
45 amps |
| 4 AWG |
70 amps |
60 amps |
| 2 AWG |
95 amps |
80 amp |
|
- Splicing extension cords must be done in such a way
that the insulation and conductivity of the wires are not compromised.
- Extension cords should not be run through water or allowed to
have connections that may be exposed to puddling water.
For more information contact: Robert
Burke, University Fire Marshal at 410.706.3494.
OSHA
Link (Electrical)