1998
2-2-98 10:30 Penthouse Smoke Detector Contractor Activated
Spray Painting
4-1-98 03:33 Basement Water Flow Switch Malfunction
4-1-98 08:45 1st Floor Smoke Detector Contractor Activated
Sanding
4-4-98 03:20 Basement Water Flow Switch Malfunction
4-6-98 15:00 1st Floor Lobby Contractor Activated (Dust)
4-27-98 06:55 Basement Water Flow Switch Malfunction
5-4-98 19:02 4th Floor Pull Station Activated by Handicap
Person Waiting for Elevator
6-9-98 17:32 Basement Water Flow Switch Malfunction
8-19-98 08:50 Basement Water Flow Switch Malfunction
8-27-98 09:16 Basement Water Flow Switch Malfunction
9-23-98 14:23 Smoke Detector in Penthouse Activated From
Steam
11-12-98 09:57 Smoke Detector in Penthouse Activated
From Steam
11-23-98 11:22 Beam Detector 2nd floor activated by electrical
contractor
11-23-98 13:46 Beam Detector 2nd floor activated by electrical
contractor
1999
2-11-99 10:05 1st Floor Manual Pull Station, activated
by housekeeping cleaning pull station
2-27-99 17:00 Basement Level Mechanical Room Water Flow
Switch on Fire Pump
9-22-99 08:15 Duct Smoke Detector Penthouse, cause unknown
12-6-99 10:55 Beam Detector 3rd floor electronics personnel
working on system and did not notify University Police. Fire
department was canceled before dispatch and building was not evacuated.
2000
1-5-00 11:35 Manual Pull Station in Coffee Shop pulled
by 3 year old child.
12-1-00 10:22 Smoke Detector basement electrical transformer
room. Carney electric personnel drilling in concrete wall
created dust which activated the smoke detector.
2001
5-3-01 23:15 Smoke Detector Computer Room under floor Activated
by
dust
5-25-01 07:08 Beam Smoke Detector Central Stairs 5th
Floor, Cause unknown.
7-9-01 13:36 Beam Smoke Detector Central Stairs 5th
Floor, Cause unknown.
2002
No Fire Alarms
2003
9-23-03 08:15 Flow Switch 4th floor.
Electronics shop supporting sprinkler outage failed to notify campus
police and fire department was called. Alarm did not sound in
building because it had been deactivated. Fire Department
Responded.
2004
No Fire Alarms
2005
No Fire Alarms
2006
7-12-06 06:00 Smoke detector cause by contractor
(Maryland Mechanical)
creating dust from drilling. Fire Department Responded.
8-21-06 12:45 Smoke detector Lower Level Computer
Room under the floor activated from dust caused by contractor
(Maryland Mechanical). Fire Department Responded.
10-18-06 08:59 Smoke detector under floor in IT Room
Lower Level activated when new air handling equipment was turned on
creating dust under the floor (Maryland Mechanical). Fire Department Responded.
12-12-06 03:37 Smoke detector 1st floor electrical
room. Whiting and Turner working in area created dust setting
off detector. Fire Department Responded.
2007
4-2-2007 14:10 Manual Pull Station hit and activated
by Whiting and Turner during demolition of Student Union. Fire
Department Responded.