Grand Parking Garage Fire Alarm Activations

1997

No fire alarms

1998

No fire alarms

1999

9-13-99  20:35  Car fire just inside entrance to the Grand Garage. BCFD responded and extinguished.  No fire alarm was activated.  Fire Department Responded.

No fire alarms

2000

1-10-00  03:15  Flow Switch Dry Sprinkler System mechanical room east side of building 1st floor.  Leaking check valve.

1-13-00  00:35  Flow Switch Dry Sprinkler System mechanical room east side of building 1st floor.  Leaking check valve from defective air compressor.

4-10-00  21:10  Flow Switch Dry Sprinkler System mechanical room east side of building 1st floor.  Defective Air compressor

10-23-00  05:25  Pressure Switch Dry Sprinkler System mechanical room east side of building 1st floor.

2001

No Fire Alarms

2002

No Fire Alarms

2003

1-26-03  16:42  Dry sprinkler system activated, cause unknown.  Fire Department Responded.

2-17-03  09:00  Dry sprinkler system activated, cause unknown.  Fire Department Responded.

8-15-03  24:00  Vehicle fire on 3rd floor set off 10th floor smoke detector.  Fire Department Responded.

8-26-03  01:30  Dry sprinkler system activated, low pressure.  Fire Department Responded.

8-28-03  10:30 Smoke was emitting from under the hood of a BMW on the South side of the 7th Level. Parking personnel opened the door, the hood was opened and exact source of smoke could not be determined. It is suspected that some type of engine fluid came in contact with a hot surface and turned into smoke.  Fire Department was not called.

2004

2-2-04  14:00  Dry sprinkler system activated.  Cause undetermined.  Fire Department Responded.

2-4-04  13:11  Dry sprinkler system activated.  Cause undetermined.  Fire Department Responded.

2-17-04  14:21  Dry sprinkler system activated.  Broken elbow on sprinkler piping in garage on the outside of the East wall of the office area.  Pipe froze during cold weather.  Fire Department Responded.

2-28-04  21:00  Dry sprinkler system activated.  Frozen pipe thawed out.  Fire Department Responded.

2005

6-24-05  05:00  Ground floor.  Pressure switch.  Defective air compressor.  Fire Department Responded.

2006

No Fire Alarms

2007

No Fire Alarms

2008