Grand Parking Garage
Fire Alarm Activations
1997
No fire alarms
1998
No fire alarms
1999
9-13-99 20:35 Car fire just
inside entrance to the Grand Garage. BCFD responded and
extinguished. No fire alarm was activated. Fire
Department Responded.
No fire alarms
2000
1-10-00 03:15 Flow Switch Dry Sprinkler System
mechanical room east side of building 1st floor. Leaking
check valve.
1-13-00 00:35 Flow Switch Dry Sprinkler System
mechanical room east side of building 1st floor. Leaking
check valve from defective air compressor.
4-10-00 21:10 Flow Switch Dry Sprinkler System
mechanical room east side of building 1st floor. Defective
Air compressor
10-23-00 05:25 Pressure Switch Dry Sprinkler System
mechanical room east side of building 1st floor.
2001
No Fire Alarms
2002
No Fire Alarms
2003
1-26-03 16:42 Dry sprinkler system activated,
cause unknown. Fire Department Responded.
2-17-03 09:00 Dry sprinkler system activated,
cause unknown. Fire Department Responded.
8-15-03 24:00 Vehicle fire
on 3rd floor set off 10th floor smoke detector. Fire
Department Responded.
8-26-03 01:30 Dry sprinkler system activated, low
pressure. Fire Department Responded.
8-28-03 10:30 Smoke was emitting
from under the hood of a BMW on the South side of the 7th Level.
Parking personnel opened the door, the hood was opened and exact
source of smoke could not be determined. It is suspected that
some type of engine fluid came in contact with a hot surface and
turned into smoke. Fire Department was not called.
2004
2-2-04 14:00 Dry sprinkler system activated.
Cause undetermined. Fire Department Responded.
2-4-04 13:11 Dry sprinkler system activated.
Cause undetermined. Fire Department Responded.
2-17-04 14:21 Dry sprinkler
system activated. Broken elbow on sprinkler piping in
garage on the outside of the East wall of the office area.
Pipe froze during cold weather. Fire Department Responded.
2-28-04 21:00 Dry sprinkler
system activated. Frozen pipe thawed out. Fire
Department Responded.
2005
6-24-05 05:00 Ground floor. Pressure
switch. Defective air compressor. Fire Department
Responded.
2006
No Fire Alarms
2007
No Fire Alarms
2008
|