1997
4-18-97 21:30 1st Floor East Pull Station Main Lobby
False Alarm.
8-26-97 13:10 2nd Floor East Smoke Detector Electrical
Room Unknown.
9-21-97 09:00 Basement West Smoke Detector Elevator Machine
Room Unknown.
1998
1-5-98 10:15 5th Floor East Smoke Detector Contractor
Activated Soldering.
1-12-98 20:20 4th Floor East Smoke Detector General Services
Activated (Dust).
3-23-98 08:30 5th Floor East Smoke Detector Rusky Contractor
Activated Soldering.
5-7-97 21:28 3rd Floor East Smoke Detector Panel Reset
on Own Unknown.
5-7-97 23:22 3rd Floor East Smoke Detector Unknown.
6-12-97 20:50 1st Floor East Smoke Detector High Voltage
Room Unknown.
6-25-98 12:05 1st Floor West Manual Pull Station Pull
Station Bumped by Student.
6-26-98 13:30 Pull Station False Alarm S.W. Stairwell
at the 2nd floor.
7-20-98 06:39 1st Floor East Smoke Detector Unknown.
8-9-98 07:13 1st Floor East Duct Detector Supply Air
Duct #1.
1999
6-12-99 09:48 1st Floor Main Entrance Pull Station Fire at 29 Green Street Building in storage shed at rear of building.
7-10-99 06:30 Smoke Detector by
West elevator 5th floor, malfunction.
7-22-99 04:50 Smoke Detector loading dock, high humidity
and moisture.
11-7-99 16:30 Smoke Detector Elevator Lobby 1st floor
maintenance personnel created dust.
11-15-99 08:58 Smoke Detector 1st floor elevator lobby,
maintenance personnel activated while removing "protective" cover.
2000
3-18-00 01:00 Smoke Detector 3rd
floor elevator lobby, defective FACP module
7-30-00 15:00 Smoke Detector 1st
floor by elevator lobby, defective FACP module.
8-31-00 15:45 Smoke Detector 1st
floor Mechanical Room, Contractor drilling hole in ceiling drilled
into fire alarm conduit causing short which activated fire alarm
system.
9-3-00 19:00 Smoke Detector 1st
Floor Elevator Machine Room, cause unknown.
2001
7-9-01 00:08 Smoke Detector 1st Floor Elevator Machine
Room, dirty detector.
7-9-01 05:43 Smoke Detector 1st Floor Elevator Machine
Room, dirty detector.
10-21-01 16:47 Smoke Detector Zone 2, Cause Unknown.
10-24-01 21:32 Smoke Detector 1st Floor High Voltage
Room, Cause Unknown (Replaced with heat detectors.)
11-2-01 00:16 Smoke Detector Zone 2, Cause unknown All
smoke detectors replaced in zone.
12-14-01 15:32 Smoke Detector Zone 2, Cause unknown.
12-14-01 16:34 Smoke Detector Zone 2, Cause unknown.
12-15-01 00:30 Smoke Detector Zone 2, Cause unknown. All
new smoke detectors installed in zone.
12-28-01 00:35 System malfunction, cause unknown.
2002
7-24-02 14:26 Flow Switch 5th floor from contractor turning
on valve without notifying electronics shop. Fire Department
Responded.
12-30-02 08:28 Smoke Detector located on first floor. Contractor
welding in area activated alarm. Fire Department Responded.
2003
4-17-03 08:30 Smoke Detector first floor elevator machine
room. Electric motor burned out activating
the smoke detector. Fire Department responded.
5-4-03 06:25 Smoke detector Elevator Machine Room for
Freight Elevator. Caused by steam from
overheated hydraulic fluid.
2004
1-6-04 10:29 Manual Pull Station
Auditorium. Contractor bumped the pull station with a trash
cart setting off the alarm. Fire Department Responded.
4-22-04 1:16 Manual Pull Station
Elevator lobby West Building Ground Floor. Cleaning person
bumped pull station causing it to activate. Fire Department
Responded.
2005
No Fire Alarms
2006
7-8-06 12:29 Heat detector 1st floor
Mechanical Room. Temperature too hot inside room. Fire
Department Responded.
9-4-06 02:40 Smoke detector 1st floor
Freight Elevator Lobby. Cause unknown. Fire Department
Responded.
3-19-2008 11:30 Malfunction ADT alarm
communicator, no fire alarm activated in building. Fire
Department Responded.